H3-08 Terminal A2 Signal Level
Setting
0
0 to 10VDC
1
-10 to 10VDC
2
4 to 20mA (factory default)
The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2
analog input. The A2 analog input can accept either a 0 to10 Vdc, -10 to +10 Vdc, or 4-20 mA signal as a reference. The Drive
also has a dipswitch (S1) on the removable terminal board that must be set for the proper reference signal into the A2 analog
input. The S1-2 dipswitch setting determines the internal resistance of the A2 input but parameter H3-08 determines how the
Drive interprets the measured signal.
DIP Switch S1 and Jumper CN15
DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in Table 19 .
Name
S1-1
RS-485 and RS-422 terminating resistance
S1-2
Input method for analog input A2
Jumper CN15 is described in this section. The jumper position of CH1 and CH2 determines the signal level of the
multi-function analog output FM and AM, respectively. The functions and positions of CN15 are shown in Table 19a .
Name
Multi-function Analog Output
CH1
CH2
Description
S1 CN15
Fig. 67 DIP Switch S1 and Jumper CN15 Location
S1
O
1
1
F
F
2
Fig. 67a DIP Switch S1 Function
Table 19 DIP Switch S1
Function
CH1
CH2
Table 19a Jumper CN15
FM
AM
Programming 98
DIP Switch S1 located on
terminal board.
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
Factory Default = OFF
OFF: 0 to 10Vdc or -10 to 10Vdc (internal resistance: 20KΩ)
ON: 4-20mA (internal resistance: 250 Ω)
Factory Default = ON
CN15
V
I
V: 0 to 10V or -10V to +10V (default)
V: 0 to 10V or -10V to +10V (default)
ON/OFF
position
Setting
Output Range
I: 4 to 20mA
I: 4 to 20mA