YASKAWA F7 Programming Manual page 189

Hide thumbs Also See for F7:
Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
Stall Prevention Selection
L3-01
During Accel
StallP Accel Sel
Stall Prevention Level
L3-02
During Acceleration
StallP Accel Lvl
Stall Prevention Limit During
L3-03
Acceleration
StallP CHP Lvl
Stall Prevention Selection
L3-04
During Deceleration
StallP Decel Sel
Stall Prevention Selection
L3-05
During Running
StallP Run Sel
Stall Prevention Level
L3-06
During Running
StallP Run Level
OV Suppression Function
L3-11
Selection
OV Inhibit Sel
OV Suppression Function
L3-12
Voltage Level
OV Inhbt VoltLvl
Denotes that parameter can be changed when the Drive is running.
* For Heavy Duty (HD) Rating: Factory Setting=150%.
Table A.1 F7 Parameter List (Continued)
Description
Stall Prevention
Selects the stall prevention method used to prevent excessive
current during acceleration.
0: Disabled - Motor accelerates at active acceleration rate. The
motor may stall if load is too heavy or accel time is too short.
1: General Purpose - When output current exceeds L3-02 level,
acceleration stops. Acceleration will continue when the output
current level falls below the L3-02 level.
2: Intelligent - The active acceleration rate is ignored. Acceleration
is completed in the shortest amount of time without exceeding
the current value set in L3-02.
This function is enabled when L3-01 is "1" or "2".
Drive rated current is 100%. Decrease the set value if stalling or
excessive current occurs with factory setting.
Sets the lower limit for stall prevention during acceleration, as a
percentage of the Drive's rated current, when operation is in the
frequency range above E1-06 (constant power region).
When using a braking resistor, use setting "0". Setting "3" is used
in specific applications.
0: Disabled - The Drive decelerates at the active deceleration rate.
If the load is too large or the deceleration time is too short, an
OV fault may occur.
1: General Purpose - The Drive decelerates at the active
deceleration rate, but if the main circuit DC bus voltage reaches
the stall prevention level (380/760Vdc), deceleration will stop.
Deceleration will continue once the DC bus level drops below
the stall prevention level.
2: Intelligent - The active deceleration rate is ignored and the Drive
decelerates as fast as possible w/o hitting OV fault level.
Range: C1-02 / 10.
3: Stall Prevention w/ Braking Resistor - Stall prevention during
deceleration is enabled in coordination with dynamic braking.
Selects the stall prevention method to use to prevent Drive faults
during run.
0: Disabled - Drive runs a set frequency. A heavy load may cause
the Drive to trip on an OC or OL fault.
1: Decel Time 1 - In order to avoid stalling during heavy loading,
the Drive will decelerate at Decel time 1 (C1-02) if the output
current exceeds the level set by L3-06. Once the current level
drops below the L3-06 level, the Drive will accelerate back to its
frequency reference at the active acceleration rate.
2: Decel Time 2 - Same as setting 1 except the Drive decelerates at
Decel Time 2 (C1-04).
When output frequency is 6Hz or less, stall prevention during
running is disabled regardless of L3-05 setting.
This parameter is enabled when L3-05 is set to "1" or "2".
Drive rated current is set as 100%.
Decrease the set value if stalling or excessive current occurs with
factory setting.
Enables or disables OV suppression function, which allows the
Drive to change the output frequency as the load changes, to
prevent OV fault.
0: Disabled
1: Enabled
Sets the DC bus voltage level at which the OV suppression
function is active.
For Normal Duty (ND) Rating: Factory Setting=120%.
Programming 181
Control Method
Setting
Factory
V/F
Range
Setting
V/F
w/
PG
0 to 2
1
A
A
Varies
by
0 to 200
A
A
Duty
Rating*
0 to 100
50%
A
A
0 to 3
1
Q
Q
0 to 2
1
A
A
Varies