Parameter
Parameter Name
No.
Digital Operator Display
o1-01
User Monitor Selection
User Monitor Sel
User Monitor Selection After
o1-02
Power-Up
Power-On Monitor
Digital Operator Display
o1-03
Selection
Display Scaling
Setting unit for frequency
parameters related to V/F
o1-04
characteristics
Display Units
LCD Brightness Adjustment
o1-05
LCD Contrast
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Description
Monitor Select
Selects which monitor will be displayed in the operation menu
upon power-up when o1-02 = 4.
Selects which monitor will be displayed upon
power-up.
1: Frequency Reference (U1-01)
2: Output Frequency (U1-02)
3: Output Current (U1-03)
4: User Monitor (set by o1-01)
Sets the units of the Frequency References (d1-01 to
d1-17), the Frequency Reference Monitors (U1-01,
U1-02, U1-05), and the Modbus communication
frequency reference.
0: Hz
1: % (100% = E1-04)
2 to 39: RPM (Enter the number of motor poles).
40 to 39999: User display.
Set the number desired at maximum
output frequency.
4 digit number
Number of digits from the right of the
decimal point
Example 1: o1-03 = 12000, will result in frequency
reference from 0.0 to 200.0 (200.0 = Fmax).
Example 2: o1-03 = 21234, will result in frequency
reference from 0.00 to 12.34 (12.34 = Fmax).
Sets the setting units related to V/F pattern frequency related
parameters (E1-04, -06, -09, -11)
0: Hertz
1: RPM
Sets the contrast of the Digital Operator LCD. A setting of "1" is
the lightest contrast and a setting of "5" is the darkest contrast.
Programming 186
Control Method
Setting
Factory
V/F
Range
Setting
V/F
w/
PG
4 to 45
6
A
A
1 to 4
1
A
A
0 to
0
A
A
39999
0 to 1
0
-
-
0 to 5
3
A
A
Open
Flux
Loop
Vector
Vector
A
A
A
A
A
A
-
A
A
A

Hide quick links: