Parameter
Parameter Name
No.
Digital Operator Display
Terminal FM Monitor
H4-01
Selection
Terminal FM Sel
H4-02
Terminal FM Gain Setting
Terminal FM Gain
H4-03
Terminal FM Bias Setting
Terminal FM Bias
Terminal AM Monitor Selec-
H4-04
tion Terminal AM Sel
H4-05
Terminal AM Gain Setting
Terminal AM Gain
H4-06
Terminal AM Bias Setting
Terminal AM Bias
Terminal FM Signal Level
H4-07
Selection
AO Level Select 1
Terminal AM Signal Level
H4-08
Selection
AO Level Select 2
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Description
Analog Outputs
Selects which monitor will be output on terminals FM and FC.
1: Frequency Reference
100% = Maximum output frequency E1-04.
2: Output Frequency
100% = Maximum output frequency E1-04.
3: Output Current
100% = Drive rated current.
5: Motor Speed
100% = Maximum output frequency E1-04.
6: Output Voltage
100% = 200/400Vac depending on Drive voltage rating.
7: DC Bus Voltage
100% = 400/800Vdc depending on Drive voltage rating.
8: Output kWatts
100% = Drive rated power.
9: Torque Reference
100% = Motor rated torque.
15:Terminal A1 Input Level
100% = 10Vdc
16:Terminal A2 Input Level
100% = 10Vdc or 20mA
17:Terminal A3 Input Level
100% = 10Vdc
18:Motor Secondary Current
100% = Motor rated secondary current.
19:Motor Excitation Current
100% = Motor rated magnetizing current.
20:SFS Output
100% = Maximum output frequency E1-04.
21:ASR Input
100% = Maximum output frequency E1-04.
22:ASR Output
100% = Maximum output frequency E1-04.
24:PID Feedback
100% = Maximum output frequency E1-04.
26:Output Voltage Reference Vq
100% = E1-05, default 240V or 480V.
27:Output Voltage Reference Vd
100% = E1-05, default 240V or 480V.
31:Not Used
32:ACR q Output (100% = Motor rated secondary current)
33:ACR d Output (100% = Motor rated magnetizing current)
36:PID Input
100% = Maximum output frequency E1-04.
37:PID Output
100% = Maximum output frequency E1-04.
38:PID Setpoint
100% = Maximum output frequency E1-04.
44:ASR Output Without Filter
45:Feedforward Control Output
100% = Motor rated secondary current.
Sets terminal FM output level when selected monitor is at 100%.
Sets terminal FM output level when selected monitor is at 0%.
Selects which monitor will be the output on terminals AM and FC.
Same function choices as H4-01.
Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.
Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 0% output.
Selects the signal level of terminal FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
Selects the signal level of terminal AM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
Programming 178
Setting
Factory
Range
Setting
V/F
1 to 45
2
A
0.0 to
100.0%
Q
1000.0
–110.0 to
0.0%
A
110.0
1 to 53
3
A
0.0 to
50.0%
Q
1000.0
–110.0 to
0.0%
A
110.0
0 or 2
0
A
0 or 2
0
A
Note: Some analog outputs are control method dependent.