Parameter
Setting
35
PID Input (Error) Polarity Change
60
DC Injection Braking
61
Speed Search 1
62
Speed Search 2
63
Field Weakening Command (Energy Savings)
64
Speed Search 3
65
Kinetic Energy Braking Ridethru N.C.
66
Kinetic Energy Braking Ridethru N.O
67
Communication Test Mode
68
High Slip Braking
69
Jog 2
6A
Drive Enable
71
Speed/Torque Control Selection
72
Zero Servo Command
77
ASR Gain Switch
78
Polarity Reversing Command for External Torque Control
Function: 3-Wire Control
Setting: 0
When one of the digital inputs is programmed for 3-Wire control, that input becomes a Forward/Reverse directional input. Whenever the
input is open, the Drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor shaft will rotate in the
reverse direction whenever a there is a Run input. The S1 and S2 digital inputs will function as a Run and Stop input respectively.
Run command
Stop command
Forward/reverse
command
Table 13 Multi-Function Input Selection (Continued)
Function
Stop
Operation
switch
switch
(NC contact)
(NO contact)
Fig. 43 Terminal Configuration for 3-Wire Control
OFF (forward)
Motor speed
Stop
Fig. 44 3-Wire Control Timing Diagram
Run command
(run on momentary close)
Stop command
S3 or S5
(stop on momentary open)
Forward/reverse command
(multi-function input)
Sequence input common
50 ms min.
Can be either ON or OFF
ON (reverse)
Forward
Reverse
Programming 71
Control Method (A1-02)
V/f with
V/f
PG
O
O
O
O
O
X
O
X
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
X
X
X
X
X
X
X
X
OFF
(stopped)
TIME
Stop
Forward
Open
Flux
Loop
Vector
Vector
O
O
O
O
O
X
O
X
X
X
O
O
O
O
O
O
O
O
X
X
O
O
O
O
X
O
X
O
X
O
X
O

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents