YASKAWA F7 Programming Manual page 192

Hide thumbs Also See for F7:
Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
Forward Torque Limit
L7-01
Torq Limit Fwd
Reverse Torque Limit
L7-02
Torq Limit Rev
Forward Regenerative
L7-03
Torque Limit
Torq Lmt Fwd Rgn
Reverse Regenerative Torque
L7-04
Limit
Torq Lmt Rev Rgn
Internal Dynamic Braking
L8-01
Resistor Protection Selection
DB Resistor Prot
Overheat Alarm Level
L8-02
OH Pre-Alarm Lvl
Overheat Pre-Alarm
L8-03
Operation Selection
OH Pre-Alarm Sel
Input Phase Loss Protection
L8-05
Selection
Ph Loss In Sel
Output Phase Loss Protection
L8-07
Ph Loss Out Sel
Output Ground Fault
L8-09
Detection Selection
Ground Fault Sel
Heatsink Cooling Fan
L8-10
Operation Selection
Fan On/Off Sel
Heatsink Cooling Fan
L8-11
Operation Delay Time
Fan Delay Time
Ambient Temperature Setting
L8-12
Ambient Temp
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Description
Torque Limit
Sets the torque limit value as a percentage of the motor rated
torque. Four individual quadrants can be set.
Output torque
Regen. state
Reverse
Regen. state
Negative torque
Hardware Protection
Selects the DB protection only when using 3% duty cycle heatsink
mount Yaskawa braking resistor. This parameter does not enable or
disable the DB function of the Drive.
0: Not Provided
1: Provided
When the cooling fin temperature exceeds the value set in this
parameter, an overheat alarm (OH) will occur.
Selects the Drive operation upon an OH pre-alarm detection.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Selects the detection of input current phase loss, power supply volt-
age imbalance, or main circuit electrostatic capacitor deterioration.
0: Disabled
1: Enabled
Selects the detection of output current open-phase.
When applied motor capacity is too small for Drive capacity,
output phase loss may be detected inadvertently. In this case, set to 0.
0: Disabled
1: 1-phase Loss Detection
2: 2/3-phase Loss Detection
Enables and disables the Drive's output ground fault detection.
0: Disabled
1: Enabled
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only when the Drive is
running and for L8-11 seconds after RUN is removed.
1: Fan Always On - Cooling fan operates whenever the Drive is
powered up.)
This parameter sets the delay time for the cooling fan turn off after
the run command is removed when L8-10 = 0.
When the Drive is installed in an ambient temperature exceeding
its rating, the Drive overload (OL2) protection level is adjusted.
Programming 184
Setting
Range
0 to 300
0 to 300
Positive torque
No. of
motor
rotations
0 to 300
Forward
0 to 300
0 to 300
45 to 60
Control Method
Factory
V/F
Setting
V/F
w/
PG
200%
-
-
200%
-
-
200%
-
-
200%
-
-
0 to 1
0
A
A
50 to
95°C
A
A
130
0 to 3
3
A
A
0 to 1
1
A
A
0 to 1
1
A
A
0 to 1
1
A
A
0 to 1
0
A
A
60sec
A
A
45°C
A
A
Open
Flux
Loop
Vector
Vector
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A