Parameter
Parameter Name
No.
Digital Operator Display
H3-06
Terminal A3 Gain Setting
Terminal A3 Gain
H3-07
Terminal A3 Bias Setting
Terminal A3 Bias
Terminal A2 Signal Level
H3-08
Selection
Term A2 Signal
Terminal A2 Function
H3-09
Selection
Terminal A2 Sel
H3-10
Terminal A2 Gain Setting
Terminal A2 Gain
H3-11
Terminal A2 Bias Setting
Terminal A2 Bias
Analog Input Filter Time
H3-12
Constant
Filter Avg Time
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Description
Sets the output level when 10V is input.
Sets the frequency reference when 0V is input.
Selects the signal level of terminal A2.
0: 0 to 10Vdc (switch S1-2 must be in the OFF position).
1: -10 to +10Vdc (switch S1-2 must be in the OFF position).
2: 4 to 20mA (switch S1-2 must be in the ON position)
Selects the function of terminal A2.
Same choices as Terminal A3 Function Selection (H3-05).
Sets the output level when 10V is input.
Sets the output level when 0V is input.
This parameter adjusts the filter on all 3 analog inputs. Increase to
add stability, decrease to improve response.
Programming 177
Control Method
Setting
Factory
V/F
Range
Setting
V/F
w/
PG
0.0 to
100.0%
A
A
1000.0
–100.0
to
0.0%
A
A
+100.0
0 to 2
2
A
A
0 to 1F
0
A
A
0.0 to
100.0%
A
A
1000.0
–100.0
to
0.0%
A
A
+100.0
0.00 to
0.03sec
A
A
2.00
Open
Flux
Loop
Vector
Vector
A
A
A
A
A
A
A
A
A
A
A
A
A
A