Direct sunlight
Device damage.
The device can overheat or materials become brittle due to UV exposure.
 Protect the device from direct sunlight.
 Make sure that the maximum permissible ambient temperature is not exceeded. Refer
4.4.2

Wall mounting

1. Prepare holes with aid of mounting bracket, see "Mounting bracket" (Page 188).
2. Fasten mounting bracket with black cushion pad to wall (torque 10 Nm).
4.4.3

Pipe mounting

1. Mount mounting bracket with cushion pad on pipe using fastening brackets/U-bolts and
2. Tighten nuts (torque: 10 Nm).
SITRANS FC430 with HART
Operating Instructions, 03/2012, A5E03361511-01
CAUTION
to the information in "Technical data" (Page 166).
supplied pipe adaptor. Note: U-bolts and other miscellaneous hardware are not supplied
with the flowmeter.
Installing/mounting
4.4 Transmitter installation
45