Emerson Rosemount 3051P Reference Manual page 83

In-line pressure transmitter with hart protocol
Hide thumbs Also See for Rosemount 3051P:
Table of Contents

Advertisement

Reference Manual
00809-0700-4001
Local operator
interface (LOI)
screen
The sensor temperature has exceeded its safe operating range.
Recommended actions
Electronics temperature beyond limits
LCD display
screen
Local operator
interface (LOI)
screen
The temperature of the electronics has exceeded its safe operating range.
Recommended actions
Electronics board parameter error
LCD display
screen
Local operator
interface (LOI)
screen
A device parameter does not match the expected value. The error does not affect
transmitter operation or analog output.
Recommended action
Replace the pressure transmitter.
Configuration buttons operator error
LCD display
screen
Local operator
interface (LOI)
screen
Device is not responding to button presses.
Rosemount 3051P
TEMP OUT LIMITS
1. Check the process and ambient conditions are within -85 to 194 °F (-65 to 90
°C).
2. Replace the pressure transmitter.
TEMP LIMITS
TEMP OUT LIMITS
1. Confirm electronics temperature is within limits of -85 to 194 °F (-65 to 90 °C).
2. Replace the pressure transmitter.
MEMRY WARN (also in advisory)
MEMORY WARN (also in advisory)
STUCK BUTTON
STUCK BUTTON
Troubleshooting
April 2020
83