Reference Manual
00809-0700-4001
Entering range points with AMS Device Manager
Procedure
1. Right click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a local operator interface (LOI)
See
Figure 2-7
Procedure
Enter values using SCROLL and ENTER buttons.
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
Procedure
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Procedure
1. Right click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure and follow the screen prompts range the
Rosemount 3051P
to rerange the transmitter using the LOI.
transmitter.
Configuration
April 2020
2, 2, 2, 2
21