Emerson Rosemount 3051P Quick Start Manual
Emerson Rosemount 3051P Quick Start Manual

Emerson Rosemount 3051P Quick Start Manual

Pressure transmitter with 4-20 ma hart protocol (revision 5 and 7)
Hide thumbs Also See for Rosemount 3051P:

Advertisement

Quick Links

Quick Start Guide
00825-0200-4007, Rev AD
May 2019
Rosemount
3051P Pressure Transmitter
®
with 4-20 mA HART
Protocol (Revision 5
and 7)

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051P

  • Page 1 Quick Start Guide 00825-0200-4007, Rev AD May 2019 ™ Rosemount 3051P Pressure Transmitter ® with 4-20 mA HART Protocol (Revision 5 and 7)
  • Page 2: Table Of Contents

    Quick Start Guide May 2019 Contents About this guide...........................3 System readiness......................... 4 Mount the transmitter........................6 Set the switches......................... 10 Connect the wiring and power up....................11 Verify transmitter configuration....................14 Trim the transmitter........................20 Safety instrumented systems..................... 23 Product Certifications.........................24 Emerson.com/Rosemount...
  • Page 3: About This Guide

    Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of the Rosemount 3051P Reference Manual for any restrictions associated with a safe installation.
  • Page 4: System Readiness

    Procedure ™ 1. Verify the latest Device Driver (DD/DTM ) is loaded on your systems to ensure proper communications. 2. Reference Emerson.com FieldCommGroup.org for the lated DD. 3. Select desired product and download the DD. a) Reference Table 1, for the correct DD.
  • Page 5 May 2019 Quick Start Guide HART Revision 5 and 7 selectable, Local Operator Interface (LOI), scaled variable, configurable alarms, expanded engineering units. Updated electronics hardware design. Intrinsic Safety temperature classification change. Quick Start Guide...
  • Page 6: Mount The Transmitter

    Figure 3-1: Transmitter Direct Mounting Do not apply torque directly to the electronics housing. To avoid damage, apply torque only to the hex-shaped process connection. A. Process connection Figure 3-2: Panel and Pipe Mounting Panel mount Pipe mount Emerson.com/Rosemount...
  • Page 7 May 2019 Quick Start Guide Mount the transmitter in liquid applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. Figure 3-3: Mounting the Transmitter in Liquid Applications In-line Mount the transmitter in gas applications Procedure...
  • Page 8 The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3-6.) Emerson.com/Rosemount...
  • Page 9 May 2019 Quick Start Guide CAUTION Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so the contaminants can drain away. Figure 3-6: Gage Low Side Pressure Port A.
  • Page 10: Set The Switches

    3. Slide the security and alarm switches into the preferred position using a small screwdriver. 4. Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements. Figure 4-1: Transmitter Electronics Board Without LCD display With LOI/LCD display A. Alarm B. Security Emerson.com/Rosemount...
  • Page 11: Connect The Wiring And Power Up

    May 2019 Quick Start Guide Connect the wiring and power up CAUTION ™ Do not tamper with or remove the electronics board in the Rosemount 3051P. This will cause permanent damage to the transmitter. Shielded twisted pair cable should be used for best results. Use 24 AWG or larger wire that does not exceed 5000 ft.
  • Page 12 C. Terminate cable shield drain wire to earth ground D. Internal ground location E. External ground location Grounding for transient terminal block Ground termination is provided on the outside of the electronics housing and inside the terminal compartment. These grounds are used when the Emerson.com/Rosemount...
  • Page 13 May 2019 Quick Start Guide transient protection terminal blocks are installed. It is recommended that 18 AWG or larger wire is used to connect housing ground to earth ground (internal or external). If the transmitter is currently not wired for power up and communication, follow procedures 1 to 7 of Connect the wiring and power up.
  • Page 14: Verify Transmitter Configuration

    Table 6-2 and the appropriate column based on your Field Revision and HART Revision for Fast Key sequences. Example Note Emerson recommends installing the latest DD to access the complete functionality. Visit Emerson.com or HARTComm.org. Figure 6-1: Traditional Interface Emerson.com/Rosemount...
  • Page 15 May 2019 Quick Start Guide Figure 6-2: Device Dashboard Note A check (✓) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure. Table 6-1: Traditional Interface Fast Keys Function Fast Key sequence ✓...
  • Page 16 HART 7 ✓ Alarm and Saturation Levels 2,2,2,5,7 2,2,2,5,7 ✓ Damping 2,2,1,2 2,2,1,1,5 2,2,1,1,5 ✓ Range Values 2,2,2 2,2,2 2,2,2 ✓ 2,2,6,1,1 2,2,7,1,1 2,2,7,1,1 ✓ Transfer Function 2,2,1,3 2,2,1,1,6 2,2,1,1,6 ✓ Units 2,2,1,1 2,2,1,1,4 2,2,1,1,4 Burst Mode 2,2,4,1 2,2,5,3 2,2,5,3 Emerson.com/Rosemount...
  • Page 17 May 2019 Quick Start Guide Table 6-2: Device Dashboard Fast Keys (continued) Function Fast Key sequence Field Revision Rev 3 Rev 5 Rev 7 HART revision HART 5 HART 5 HART 7 Custom Display Configuration 2,2,3 2,2,4 2,2,4 Date 2,2,6,1,4 2,2,7,1,3 2,2,7,1,4 Descriptor...
  • Page 18 Quick Start Guide May 2019 Figure 6-3: Internal and External LOI Buttons A. Internal buttons B. External buttons Note Figure 7-1 to confirm external button functionality. Table 6-3: LOI Button Operation Button Left SCROLL Right ENTER Emerson.com/Rosemount...
  • Page 19 May 2019 Quick Start Guide Figure 6-4: LOI Menu Assign PV HART Revision 6.3.1 Switch HART revision mode ® If the HART configuration tool is not capable of communicating with HART ™ Revision 7, the Rosemount 3051P will load a Generic Menu with limited capability.
  • Page 20: Trim The Transmitter

    Trimming with a Field Communicator Procedure 1. Connect the Field Communicator, see Connect the wiring and power for instructions. ® 2. Follow the HART menu to perform the desired zero trim. Emerson.com/Rosemount...
  • Page 21 May 2019 Quick Start Guide Table 7-1: Zero Trim Fast Keys Analog zero (set 4 mA) Digital zero Fast Key sequence 3, 4, 2 3, 4, 1, 3 Trimming with configuration buttons A zero trim is to be performed using one of the three possible sets of external configuration buttons located under the top tag.
  • Page 22 Perform trim with digital zero (option DZ) Use this procedure to perform a Zero Trim with digital zero. Procedure 1. Set the transmitter pressure. 2. Press and hold the zero button for two seconds to perform a digital zero trim. Emerson.com/Rosemount...
  • Page 23: Safety Instrumented Systems

    May 2019 Quick Start Guide Safety instrumented systems ™ For safety certified installations, refer to the Rosemount 3051P Reference Manual for installation procedure and system requirements. Quick Start Guide...
  • Page 24: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. North America E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
  • Page 25 May 2019 Quick Start Guide Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CSA Std C22.2 No. 25-1966, CSA Std C22.2 No. 30-M1986, CAN/CSA-C22.2 No. 94-M91, CSA Std C22.2 No. 142-M1987, CAN/CSA-C22.2 No. 157-92, CSA Std C22.2 No. 213-M1987, ANSI- ISA-12.27.01-2003 Markings: Intrinsically Safe Class I, Division 1 when connected in accordance with Rosemount drawing 02088-1024, Temperature Code T4;...
  • Page 26 1. This apparatus is not capable of withstanding the 500 V insulation test required by EN60079-15. This must be taken into account when installing the apparatus. ND ATEX Dust Certificate: BAS01ATEX1427X Standards: EN60079-0:2012 + A11:2013, EN60079-31:2009 Markings: II 1 D Ex t IIIC T50 °C T50060 °C Da Emerson.com/Rosemount...
  • Page 27 May 2019 Quick Start Guide Special Conditions for Safe Use (X): 1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 2. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
  • Page 28 1. When fitted with a transient suppression terminal block, the Model 2088 is incapable of passing the 500 V isolation test. This must be taken into account during installation. NK IECEx Dust Certificate: IECEx BAS12.0073X Standards: IEC60079-0:2011, IEC60079-31:2008 Markings: Ex t IIIC T50 °C T 60 °C Da Emerson.com/Rosemount...
  • Page 29 May 2019 Quick Start Guide ® Parameter HART Voltage U 36 V Current I 24 mA Special Conditions for Safe Use (X): 1. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66. 2.
  • Page 30 1. See certificate for special conditions. IM EAC Intrinsic Safety Certificate: TC RU C-US.AA87.B.00534 Markings: 0Ex ia IIC T4 Ga X, T4(–55 °C ≤ T ≤ +70 °C) Special Condition for Safe Use (X): 1. See certificate for special conditions. Emerson.com/Rosemount...
  • Page 31 May 2019 Quick Start Guide Combinations K1 Combination of E1, I1, and N1 K5 Combination of E5 and I5 K6 Combination of E6 and I6 K7 Combination of E7, I7, N7, and NK KB Combination of K5 and K6 KD Combination of E1, I1, K5 and K6 KM Combination of EM and IM Conduit plugs and adapters IECEx Flameproof and Increased Safety...
  • Page 32 2. The blanking plug shall not be used with an adapter. 3. Blanking Plug and Threaded Adapter shall be either NPT or Metric thread forms. G½ thread forms are only acceptable for existing (legacy) equipment installations. Emerson.com/Rosemount...
  • Page 33 May 2019 Quick Start Guide Declaration of Conformity Quick Start Guide...
  • Page 34 Quick Start Guide May 2019 Emerson.com/Rosemount...
  • Page 35 May 2019 Quick Start Guide Quick Start Guide...
  • Page 36 O: Indicate that said hazardous substance in all of the homogeneous materials for this part is below the limit requirement of GB/T 26572. GB/T 26572 X: Indicate that said hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement of GB/T 26572. Emerson.com/Rosemount...
  • Page 37 May 2019 Quick Start Guide 9.10 Installation drawings Installation drawing 02088-1024 Quick Start Guide...
  • Page 38 Quick Start Guide May 2019 Emerson.com/Rosemount...
  • Page 39 May 2019 Quick Start Guide Quick Start Guide...
  • Page 40 Quick Start Guide May 2019 Emerson.com/Rosemount...
  • Page 41 May 2019 Quick Start Guide Quick Start Guide...
  • Page 42 Quick Start Guide May 2019 Emerson.com/Rosemount...
  • Page 43 May 2019 Quick Start Guide Quick Start Guide...
  • Page 44 The Emerson logo is a Twitter.com/Rosemount_News trademark and service mark of Emerson Electric Facebook.com/Rosemount Co. Rosemount is mark of one of the Emerson Youtube.com/user/ family of companies. All other marks are the RosemountMeasurement property of their respective owners.