6. How to Install
The harmonics do not affect the power con-
sumption directly but increase the heat losses
in the installation (transformer, cables). Con-
sequently, in plants with a high percentage of
rectifier load, maintain harmonic currents at a
low level to avoid overload of the transformer
and high temperature in the cables.
Harmonic currents compared to the RMS input
current:
6
To ensure low harmonic currents, the frequency converter is equipped with intermediate circuit
coils as standard. This normally reduces the input current I
The voltage distortion on the mains supply
depends on the size of the harmonic currents
multiplied by the mains impedance for the fre-
quency in question. The total voltage distor-
tion THD is calculated on the basis of the
individual voltage harmonics using this formu-
la:
6.10.1. Residual Current Device
You can use RCD relays, multiple protective earthing or earthing as extra protection, provided that
local safety regulations are complied with.
If an earth fault appears, a DC content may develop in the faulty current.
If RCD relays are used, you must observe local regulations. Relays must be suitable for protection
of 3-phase equipment with a bridge rectifier and for a brief discharge on power-up see section
Earth Leakage Current
126
NB!
Some of the harmonic currents might disturb communication equipment connected
to the same transformer or cause resonance in connection with power-factor cor-
rection batteries.
for further information.
MG.33.B9.02 - VLT
I
RMS
I
1
I
5
I
7
I
11-49
by 40%.
RMS
2
2
THD
U
U
% =
+
5
7
(U
% of U)
N
®
is a registered Danfoss trademark
FC 300 Design Guide
Input current
1.0
0.9
0.4
0.2
< 0.1
2
U
+ ...
+
N