The endpoints P1 and P2 are defined by the following parameters depending on which analog or
pulse input is used
P1 = (Minimum input value, Minimum reference value)
Minimum reference val-
ue
Minimum input value
P2 = (Maximum input value, Maximum reference value)
Maximum reference val-
ue
Maximum input value

3.2.11. Dead Band Around Zero

In some cases the reference (in rare cases also the feedback) should have a Dead Band around
zero (i.e. to make sure the machine is stopped when the reference is "near zero").
To make the dead band active and to set the amount of dead band, the following
settings must be done:
The size of the Dead Band is defined by either P1 or P2 as shown in the graph below.
28
Analog 53
Analog 53
S201=OFF
S201=ON
Par. 6-14
Par. 6-14
Par. 6-10 [V] Par. 6-12
[mA]
Par. 6-15
Par. 6-15
Par. 6-11 [V] Par. 6-13
[mA]
Either Minimum Reference Value (see table above for relevant parameter) or Maximum
Reference Value must be zero. In other words; Either P1 or P2 must be on the X-axis in
the graph below.
And both points defining the scaling graph are in the same quadrant.
MG.33.B9.02 - VLT
Analog 54
Analog 54
Pulse Input
S202=OFF
S202=ON
29
Par. 6-24
Par. 6-24
Par. 5-52
Par. 6-20 [V] Par. 6-22
Par. 5-50
[mA]
[Hz]
Par. 6-25
Par. 6-25
Par. 5-53
Par. 6-21 [V] Par. 6-23
Par. 5-51
[mA]
[Hz]
®
is a registered Danfoss trademark
FC 300 Design Guide
Pulse Input 33
Par. 5-57
Par. 5-55 [Hz]
Par. 5-58
Par. 5-56 [Hz]