FC 300 Design Guide
Mains Supply 3 x 380 - 500 VAC (FC 302), 3 x 380 - 480 VAC (FC 301)
FC 301/FC 302
High/ Normal Load*
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
P11K
HO
Typical Shaft out-
11
put [kW]
Enclosure IP21
B1
Enclosure IP55, 66
B1
Output current
Continuous
24
(3 x 380-440 V) [A]
Intermittent
(60
sec overload)
38.4
(3 x 380-440 V) [A]
Continuous
21
(3 x 440-500 V) [A]
Intermittent
(60
sec overload)
33.6
(3 x 440-500 V) [A]
Continuous KVA
16.6
(400 V AC) [KVA]
Continuous KVA
(460 V AC) [KVA]
Continuous
(3 x 380-440 V )
22
[A]
Intermittent
(60
sec overload)
35.2
(3 x 380-440 V )
[A]
Continuous
19
(3 x 440-500 V) [A]
Intermittent
(60
sec overload)
30.4
(3 x 440-500 V) [A]
Max.
cable
size
16/6
[mm
2
/ AWG]
2)
Max. pre-fuses [A]
63
1
Estimated
power
loss
291
at rated max. load
[W]
4)
Weight,
enclosure IP21, IP
23
55, 66 [kg]
4)
0.977
Efficiency
MG.33.B9.02 - VLT
®
is a registered Danfoss trademark
P15K
P18K
NO
HO
NO
HO
15
15
18.5
18.5
B1
B2
B1
B2
32
32
37.5
37.5
35.2
51.2
41.3
60
27
27
34
34
29.7
43.2
37.4
54.4
22.2
22.2
26
26
21.5
27.1
29
29
34
34
31.9
46.4
37.4
54.4
25
25
31
31
27.5
40
34.1
49.6
16/6
35/2
63
63
392
379
465
444
23
27
0.978
0.979
4. FC 300 Selection
P22K
NO
HO
NO
22.0
22.0
30.0
B2
B2
44
44
61
48.4
70.4
67.1
40
40
52
44
64
57.2
30.5
30.5
42.3
31.9
41.4
40
40
55
44
64
60.5
36
36
47
39.6
57.6
51.7
35/2
80
525
547
739
27
0.978
59
4
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?