FC 300 Design Guide
Active Reference and Configuration Mode
The active reference can be either the local reference or the remote reference.
In par. 3-13
[2].
To permanently select the remote reference select
to
[0] (default) the reference site will depend on which mode is active. (Hand Mode or Auto Mode).
Hand On
Auto
LCP Keys
Hand
Hand -> Off
Auto
Auto -> Off
All keys
All keys
The table shows under which conditions either the Local reference or the Remote reference is
active. One of them is always active, but both can not be active at the same time.
Par. 1-00
Torque or Process Control) is used when the Remote reference is active (see table above for the
conditions).
Par. 1-05
when the Local reference is made active.
Reference Handling
Local Reference
Remote Reference
130BP046.10
Reference Site
the local reference can be permanently selected by selecting
Reference Site
Par. 3-13
Linked to Hand / Auto
Linked to Hand / Auto
Linked to Hand / Auto
Linked to Hand / Auto
Local
Remote
Configuration Mode
determines what kind of application control principle (i.e. Speed,
Local Mode Configuration
determines the kind of application control principle that is used
MG.33.B9.02 - VLT
®
is a registered Danfoss trademark
3. Introduction to FC 300
Remote
Linked to Hand/Au-
[1]. By selecting
Active Reference
Local
Local
Remote
Remote
Local
Remote
3
Local
25