Table 8-26: BLOCK_ERR Conditions
Condition
number
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
8.9.6 
Modes
The PID function block supports the following modes:
Manual (Man): The block output (OUT) may be set manually.
Automatic (Auto): The SP may be set manually, and the block algorithm
calculates OUT.
Cascade (Cas): The SP is calculated in another block and is provided to the PID
block through the CAS_IN connection.
RemoteCascade (RCas): The SP is provided by a host computer that writes to
the RCAS_IN parameter.
RemoteOutput (Rout): The OUT is provided by a host computer that writes to
the ROUT_IN parameter.
Local Override (LO): The track function is active. OUT is set by TRK_VAL. The
BLOCK_ERR parameter shows Out of service.
Initialization Manual (IMan): The output path is not complete (for example, the
cascade-to-slave path might not be open). In IMan mode, OUT tracks
BKCAL_IN.
Rosemount OCX8800A
Condition name and description
Other
Block Configuration Error: The BY_PASS parameter is not configured
and is set to 0, the SP_HI_LIM is less than the SP_LO_LIM, or the
OUT_HI_LIM is less than the OUT_LO_LIM.
Link Configuration Error
Simulate Active
Local Override: The actual mode is LO.
Device Fault State Set
Device Needs Maintenance Soon
Input Failure/Process Variable has Bad Status: The parameter linking to
IN is indicating a Bad status.
Output Failure
Memory Failure
Lost Static Data
Lost NV Data
Readback Check Failed
Device Needs Maintenance Now
Power Up
Out of Service: The actual mode is out of service.
F
Fieldbus
OUNDATION
December 2022
181