Figure 2-8: Signal Wiring or Cable
A. Strip wire ends 3/16 in. (4.8 mm) typical
B. Stud size #10
C. Heat shrink tubing 2 in. (50.8 mm) long ½ in. (12.7 mm) size
D. 7.0-in.(177.8 mm) long PTFE tubing, 0.042-in. ID (Cut off drain wire at probe end
E. ¾ national pipe thread (NPT) hub size, liquid-tight strain relief connector
F. Heat shrink tubing 2 in. (50.8 mm) long ½ in. (12.7 mm) size
G. 8 twisted pairs 24 AWG, stranded, insulated, tinned copper conductors, 400 °F
H. Ferrule, uninsulated
I. Overall cable length by customer 150-ft. (45.7 m) maximum
J. Heat shrink tubing 1 in. (25.4 mm) long, 3/16 in. (4.8 mm) size
K. Typical on both ends of wiring
L. 2.0 ± 0.25 typical
M. For RFI/CE compliance, the connector must provide 360 degrees of electrical
Rosemount OCX8800A
of shield.)
(200 °C), 300 volts, with overall braid of 34 AWG tinned copper, uninsulated
drain wire
contact to the cable shield.
Install
December 2022
41