2/2008
EN50160 Evaluation System Configuration and Status Registers
Table C–4: EN50160 Evaluation System Configuration and Status Registers
Register Number
3900
1
3901
1
3902
1
3903
1
3904
1
3905
1
3906
1
3907
1
3908
1
3909
1
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
All of the EN50160 data is stored in non-volatile memory once per
hour or when an event occurs. In the event of a meter reset, up to one
hour of routine meter evaluation data will be lost.
Table C–4 lists registers for system configuration and status
evaluation.
Enable/Disable EN50160 Evaluation
0 = Disable (default)
1 = Enable
Nominal Voltage, (copied from register 3234 for reference)
Default = 230
Voltage Selection for 4-Wire Systems
0 = Line-to-Neutral (default)
1 = Line-to-Line
Nominal Frequency, Hz (copied from register 3208 for reference)
Default = 60
Frequency configuration
0 = system with synchronous connection to interconnected system
(default)
1 = system without synchronous connection to interconnected system
First Day of Week
1 = Sunday
2 = Monday (default)
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
Definition of Interruption
0 – 10% Nominal (default = 1)
Allowable Range of Slow Voltage Variations
1 – 20% Nominal (default = 10)
Reserved
Reserved
ACCESS 9340 and 9360 Meters
Appendix C—EN50160 Evaluation
Description
EN–229