PMCM-9340D-0208
2/2008
Table A–3: Abbreviated Register List
Reg
Name
Alternate Displacement
1173
Power Factor, Phase B
Alternate Displacement
1174
Power Factor, Phase C
Alternate Displacement
1175
Power Factor, Total
1s Metering — Frequency
1180
Frequency
Power Quality
THD
THD/thd Current,
1200
Phase A
THD/thd Current,
1201
Phase B
THD/thd Current,
1202
Phase C
THD/thd Current,
1203
Phase N
THD/thd Voltage,
1207
Phase A-N
THD/thd Voltage,
1208
Phase B-N
THD/thd Voltage,
1209
Phase C-N
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
Scale
Units
0.001
(-32,768 if N/A)
0.001
(-32,768 if N/A)
0.001
0.01Hz
2,300 – 6,700
0.10Hz
3,500 – 4,500
(-32,768 if N/A)
0.10%
0.10%
0.10%
0.10%
(-32,768 if N/A)
0.10%
(-32,768 if N/A)
0.10%
(-32,768 if N/A)
0.10%
(-32,768 if N/A)
ACCESS 9340 and 9360 Meters
Appendix A—Meter Register List
Range
Derived using only fundamental frequency of
the real and apparent power (4-wire system
0 – 2,000
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
Derived using only fundamental frequency of
the real and apparent power (4-wire system
0 – 2,000
only). The reported value is mapped from 0-
2000, with 1000 representing unity, values
below 1000 representing lagging, and values
above 1000 representing leading.
Derived using only fundamental frequency of
the real and apparent power. The reported
value is mapped from 0-2000, with 1000
0 – 2,000
representing unity, values below 1000
representing lagging, and values above 1000
representing leading.
(50/60Hz)
Frequency of circuits being monitored. If the
frequency is out of range, the register is -
32,768.
(400Hz)
Total Harmonic Distortion, Phase A Current
0 – 32,767
See register 3227 for THD/ thd definition
Total Harmonic Distortion, Phase B Current
0 – 32,767
See register 3227 for THD/ thd definition
Total Harmonic Distortion, Phase C Current
0 – 32,767
See register 3227 for THD/ thd definition
Total Harmonic Distortion, Phase N Current
0 – 32,767
(4-wire system only)
See register 3227 for THD/ thd definition
Total Harmonic Distortion Phase A-N
0 – 32,767
(4-wire system only)
See register 3227 for THD/ thd definition
Total Harmonic Distortion Phase B-N
0 – 32,767
(4-wire system only)
See register 3227 for THD/ thd definition
Total Harmonic Distortion Phase C-N
0 – 32,767
(4-wire system only)
See register 3227 for THD/ thd definition
Notes
EN–125