Siemens ACCESS 9340 Reference Manual page 189

Table of Contents

Advertisement

PMCM-9340D-0208
2/2008
Table A–6: Registers for Alarm Position Counters
Reg
Name
Alarms — Template 2
Base
Unique Identifier
Base +2
Enable/Disable, Priority
Base +3
Label
Base +11
Alarm test list
Table A–7: Abbreviated Floating-Point Register List
Reg
1s Metering – Current
11700
Current, Phase A
11702
Current, Phase B
11704
Current, Phase C
11706
Current, Neutral
11708
Current, Ground
11710
Current, 3-Phase Average
1s Metering – Voltage
11712
Voltage, A-B
11714
Voltage, B-C
11716
Voltage, C-A
11718
Voltage, L-L Average
11720
Voltage, A-N
11722
Voltage, B-N
11724
Voltage, C-N
11726
Voltage, N-G
11728
Voltage, L-N Average
1s Metering – Power
11730
Real Power, Phase A
11732
Real Power, Phase B
11734
Real Power, Phase C
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
Scale Units
Name
Range
Bits 00 – 07 = Level (0 – 9)
0 –
Bits 08 – 15 = Alarm Type
0xFFFFFFFF
Bits 16 – 31 = Test Register
MSB: 0 – FF
MSB: 0x00 = Disable; 0xFF = Enable
LSB: 0 – 3
LSB: Specifies the priority level 0 – 3
ASCII
16 Characters
0 – 74
Alarm test list (position # in the normal alarm list)
Units
Amps
RMS
Amps
RMS
Amps
RMS
RMS
Amps
4-wire system only
RMS
Amps
4-wire system only
Amps
Calculated mean of Phases A, B & C
Volts
RMS Voltage measured between A & B
Volts
RMS Voltage measured between B & C
Volts
RMS Voltage measured between C & A
Volts
RMS 3 Phase Average L-L Voltage
RMS Voltage measured between A & N
Volts
4-wire system only
RMS Voltage measured between B & N
Volts
4-wire system only
RMS Voltage measured between C & N
Volts
4-wire system only
RMS Voltage measured between N & G
Volts
4-wire system with 4 element metering only
Volts
RMS 3-Phase Average L-N Voltage
Real Power (PA)
W
4-wire system only
Real Power (PB)
W
4-wire system only
Real Power (PC)
W
4-wire system only
ACCESS 9340 and 9360 Meters
Appendix A—Meter Register List
Notes
Notes
EN–181