ACCESS 9340 and 9360 Meters
Appendix A—Meter Register List
Table A–6: Registers for Alarm Position Counters
Reg
Name
Alarms — Template 1
Base
Unique Identifier
Base +2
Enable/Disable, Priority
Base +3
Label
Base +11
Pickup Value
Base +12
Pickup Delay
Base +13
Dropout Value
Base +14
Dropout Delay
Base +15
Reserved
Base +16
Datalog Specifier
EN–180
Scale Units
Range
0 –
0xFFFFFFFF
MSB: 0 – FF
LSB: 0 – 3
ASCII
A-F
Units/Scale
0 – 32,767
0 – 32,767
1s Cycle
0 – 999
0 – 999
A-F
Units/Scale
0 – 32,767
0 – 32,767
1s Cycle
0 – 999
0 – 999
0 –
0xFFFFFFFF
Bits 00 – 07 = Level (0 – 9)
Bits 08 – 15 = Alarm Type
Bits 16 – 31 = Test Register
For Disturbance alarms Test Register is:
1 = Vab
2 = Vbc
3 = Vca
4 = Van
5 = Vbn
6 = Vcn
7 = Vng
8 = Ia
9 = Ib
10 = Ic
11 = In
For Unary Alarms, Test Register is:
1 = End of Incremental Energy Interval
2 = End of Power Demand Interval
3 = End of 1s Meter Update Cycle
4 = Reserved
5 = Power up/ Reset
MSB:
0x00 = Disabled (Default)
0xFF = Enabled
LSB: Specifies the priority level 0 – 3
16 Characters
Does not apply to digital or unary alarms
Standard Speed Alarms
Disturbance Alarms
Does not apply to digital or unary alarms.
Does not apply to digital or unary alarms.
Standard Speed Alarms
Disturbance Alarms
Does not apply to digital or unary alarms.
Reserved for future development
Bit 00 = Datalog #1
Bit 01 = Datalog #2 (PM850, 9360DC)
Bit 02 = Datalog #3 (PM850, 9360DC)
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
PMCM-9340D-0208
2/2008