ACCESS 9340 and 9360 Meters
Appendix A—Meter Register List
Table A–3: Abbreviated Register List
Reg
Name
Communications
Communications — RS485
3400
Protocol
3401
Address
3402
Baud Rate
3403
Parity
3410
Packets To This Unit
3411
Packets To Other Units
Packets With Invalid
3412
Address
3413
Packets With Bad CRC
3414
Packets With Error
Packets With Illegal
3415
Opcode
Packets With Illegal
3416
Register
Invalid Write
3417
Responses
Packets With Illegal
3418
Counts
Packets With Frame
3419
Error
3420
Broadcast Messages
3421
Number Of Exceptions
Messages With Good
3422
CRC
3423
Modbus Event Counter
EN–152
Scale
Units
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
Range
0 = Modbus (default)
0 – 2
1 = Jbus
Valid Addresses: (Default = 1)
0 – 255
Modbus: 0 – 247
Jbus: 0 – 255
3 = 9600 (default)
0 – 5
4 = 19200
5 = 38400
0 = Even (default)
0 – 2
1 = Odd
2 = None
Number of valid messages addressed to this
0 – 32,767
unit
Number of valid messages addressed to other
0 – 32,767
units
Number of messages received with invalid
0 – 32,767
address
0 – 32,767
Number of messages received with bad CRC
0 – 32,767
Number of messages received with errors
Number of messages received with an illegal
0 – 32,767
opcode
Number of messages received with an illegal
0 – 32,767
register
0 – 32,767
Number of invalid write responses
Number of messages received with an illegal
0 – 32,767
count
Number of messages received with a frame
0 – 32,767
error
0 – 32,767
Number of broadcast messages received
0 – 32,767
Number of exception replies
Number of messages received with a good
0 – 32,767
CRC
0 – 32,767
Modbus Event Counter
PMCM-9340D-0208
2/2008