ACCESS 9340 and 9360 Meters
Chapter 5—Input/Output Capabilities
EN–60
The digital input has three operating modes:
Normal—Use the normal mode for simple on/off digital inputs. In
normal mode, digital inputs can be used to count KY pulses for
demand and energy calculation.
Demand Interval Synch Pulse—you can configure any digital
input to accept a demand synch pulse from a utility demand meter
(see "Demand Synch Pulse Input" on page 61 of this chapter for
more about this topic). For each demand profile, you can
designate only one input as a demand synch input.
Conditional Energy Control—you can configure one digital input
to control conditional energy (see "Energy Readings" on page 52
in Chapter 4—Metering Capabilities for more about conditional
energy).
NOTE: By default, the digital input is named DIG IN S02 and is set up
for normal mode.
For custom setup, use ION Setup to define the name and operating
mode of the digital input. The name is a 16-character label that
identifies the digital input. The operating mode is one of those listed
above. See the ION Setup online help for instructions on device set
up of the meter.