Siemens ACCESS 9340 Reference Manual page 158

Table of Contents

Advertisement

ACCESS 9340 and 9360 Meters
Appendix A—Meter Register List
Table A–3: Abbreviated Register List
Reg
Name
Wiring Error Detection
3260
4
3261
Scaling Error
EN–150
Scale
Units
Binary
Binary
0x0000 – 0x003F
© 2008 Siemens Energy & Automation, Inc. All Rights Reserved
Range
0 = Normal
1 = Error
Bit 00 = CTa reversed polarity
Bit 01 = CTb reversed polarity
Bit 02 = CTc reversed polarity
Bit 03 = Reserved
Bit 04 = Move CTa to CTb
Bit 05 = Move CTb to CTc
0x0000 –
Bit 06 = Move CTc to Cta
0xFFFF
Bit 07 = Move CTa to CTc
Bit 08 = Move CTb to Cta
Bit 09 = Move CTc to CTb
Bit 10 = Move CTa to CTb & reverse polarity
Bit 11 = Move CTb to CTc & reverse polarity
Bit 12 = Move CTc to CTa & reverse polarity
Bit 13 = Move CTa to CTc & reverse polarity
Bit 14 = Move CTb to CTa & reverse polarity
Bit 15 = Move CTc to CTb & reverse polarity
Indicates potential over range due to scaling
error
0 = Normal
1 = Error
Bit 00 = Summary Bit (On if any other bit is on)
Bit 01 = Scale A – Phase Current Error
Bit 02 = Scale B – Neutral Current Error
Bit 03 = Unused
Bit 04 = Scale D – Phase Voltage Error
Bit 05 = Scale E – Neutral Voltage Error
Bit 06 = Scale F – Power Error