Viking Oxeo PR LCP Operator's Manual page 99

Inert gas extinguishing system
Table of Contents

Advertisement

Fault description
The electrical release
device is not activated
despite triggering
(LED lights up)
The line fault "electri-
cal release device" is
shown
No pressure is applied
behind the pressure
reducer
No pressure or the
incorrect pressure is
applied behind the
pressure reducer
The adapter connec-
tion is leaky
The shuttle non-return
valve is leaky or not
functioning
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en
Cause
The polarization of the
electrical connection is
incorrect
The electrical release
device is defective
The connection line is
inverted (commission-
ing)
The control module is
defective (maintenance)
The line connection is
faulty (short circuit or
wire break)
A foreign object or dirt
is blocking the inlet to
the pressure reducer
The pressure reducer is
incorrectly set
The pressure reducer is
defective
The seal is defective or
not present
The seal fitting is dirty
or the ball is stuck
Remedy
Check the cable con-
nection and correct it
Replace the electrical
release device
Correct the connec-
tion
Replace the control
module
Detect the faulty con-
nection
Perform repairs
Check the connection
components (adapter,
valve output); clean
and remount if neces-
sary
Check and set the set-
ting
If the pressure reducer
cannot be set, replace
it
Check the seal;
replace if necessary
Replace the shuttle
non-return valve
Malfunctions
Personnel
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
Authorized Distributor
97