Are all structural openings (windows, doors) closed or fitted with operational automatic locking
devices?
Are the means of escape of the protection zones unobstructed?
Are additional fire loads (e.g. boxes, packaging material) removed from the protection zone?
Have all information signs of the system been attached and is the information they contain eas-
ily readable?
Does the fire detection and suppression control panel show power supply voltage?
Is no malfunction displayed on the fire detection and suppression control panel?
If one or several of these inspection questions cannot be answered with "Yes" or if you are uncertain
as to the correct answer, please contact an Authorized Distributor immediately. Contact can be
established through the manufacturer; see page 2.
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en
Inspections
85