Appendix A - Weekly Inspections - Viking Oxeo PR LCP Operator's Manual

Inert gas extinguishing system
Table of Contents

Advertisement

Appendix A - Weekly Inspections

13
Specification
Yes
NO
Do the contact pressure gauges show system pressure?
At 59 °F (15 °C) the pressure is 2901 psi (200 bar) or 4351 psi (300 bar) depending on
the system.
Have all extinguishing cylinders been fitted with the intended release devices?
Ensure that the extinguishing cylinders are attached correctly.
Do the extinguishing cylinders contain the required quantity - including any potential
reserve quantities - in accordance with the installation certificate?
Are the extinguishing cylinders, valves, release devices, hoses, selector valves, non-
return valve, and pneumatic pilot lines in good condition?
Are the electric lines leading to the fire detection and suppression control panel and
the equipotential bonding connected properly and in good condition?
Are the pipe systems components, supports, and extinguishing nozzles intact?
Are the alarm devices intact?
Are the manual releases accessible and in good condition?
Are the automatic fire detectors intact?
Are the extinguishing nozzle discharge zones unobstructed?
Are all wall breakthroughs sealed off to the adjoining zones?
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en