Operation
5. Notify the Authorized Distributor or service personnel authorized by the Authorized Dis-
tributor so that the operational readiness of the system can be restored.
Do not replace extinguishing agent containers without authorization even if they are empty.
6. Perform function checks.
Steps after faulty release
Personnel:
Person in charge of the system
Protective equipment:
Self-contained breathing apparatus
If no fire has occurred, the all-clear from the fire department is not necessary in case of a faulty
release of the system. The fire department must ensure that a sufficient concentration of oxy-
gen exists in the extinguishing zones.
In addition to the instructions specified below, all applicable local regulations regarding the behavior
in the event of an activation of automatic fire suppression systems must be observed.
1. Make sure that no unauthorized persons can enter the affected premises before they have
been cleared for access by the person in charge of the system.
2. Enter the extinguishing zone carrying substitute extinguishing agents (e.g. fire extin-
guisher) and open windows and doors to ventilate the zone.
Have the extinguishing agent extracted by the fire department in lower situated premises where suf-
ficient ventilation cannot be achieved.
3. Do not clear the extinguishing zone for access until it has been sufficiently ventilated and
an oxygen concentration of at least 20.9% has been reached.