10.2 Fault indicators

Possible malfunctions are indicated on the fire detection and suppression control panel.
This manual does not include a description of the fire detection and suppression control panel. Fol-
low the separate instructions for use of the fire detection and suppression control panel.
Other indications of malfunctions such as extinguishing agent leaks are provided by the contact
pressure gauge fitted on the extinguishing agent containers.

10.3 Malfunction table

Protective equipment:
Industrial hard hat
Safety goggles
Safety gloves
Safety footwear
The electric control device is referred to as "EST" in the following tables.
The fire detection and suppression control panel is referred to as "FACP" in the following tables.
10.3.1Extinguishing agent container with quick release valve QRV
Fault description
The value indicated is
too low or too high
Loss indication shown
on the EST/FACP
Line breakage or short
circuit in the loss moni-
toring is shown on the
EST/FACP
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en
Cause
The room temperature is
too low or too high
At least one extinguish-
ing agent container is
leaky
(See above)
Line or cable connec-
tion is faulty
Remedy
Adjust the room air
conditioning
Identify the extin-
guishing agent con-
tainer
Replace the extin-
guishing agent con-
tainer immediately
Identify damaged
area and repair it
Malfunctions
Personnel
Person in charge of the
system
Person in charge of the
system
Authorized Distributor
Authorized Distributor
95