3.2 Storing extinguishing agent containers

Store reserve extinguishing agent cylinders under the following conditions:
Do not store outdoors.
Store in a dry, dust-free environment.
Do not expose to aggressive media.
Protect against direct exposure to sunlight.
Avoid mechanical vibrations/shocks.
Avoid condensation moisture.
Storage temperature: -4 to +131 °F (-20 to +55 °C).
Store with the valve protection cap in place.
Always store in the supplied transport frame or lying on the supplied pallet.
Observe national regulations on the storage of extinguishing agent cylinders.
If stored for more than 3 months, regularly check the general condition of all extinguishing
agent cylinders. If necessary, contact an authorized distributor or service personnel autho-
rized by the authorized distributor and have damaged or corroded extinguishing agent
containers replaced. Contact via the manufacturer if possible (see page 2).
WARNING Risk of injury from illegible symbols
Over the course of the storage period, labels and signs can become soiled or illegible in some
other way, which may result in risks no longer being detected and the necessary operating
instructions no longer being followed. This will lead to a risk of injury.
• Keep all safety, warning and operating instructions easily legible at all times.
• Replace any damaged signs or labels immediately (or have them replaced).
There might be notices on storage on the packaging items that go beyond the requirements
stipulated here. Observe them accordingly.