Inert gas extinguishing system
Table of Contents

Advertisement

Safety
Oxygen deficiency
WARNING Risk of death due to oxygen deficiency
If the extinguishing agent concentration exceeds 52% by vol. (LOAEL), the extinguish-
ing agent can have a toxic effect due to the reduced oxygen concentration. A danger
of asphyxiation exists with extinguishing agent concentrations above 62% by vol.
• Avoid inhaling vapors, aerosols, and atomized spray.
• Exit the extinguishing zone without delay and within the pre-warning time in case of an
• Do not reenter the extinguishing zone after a fire until the fire department has given the all-
• Comply with the safety data sheet for the extinguishing agent.
Extinguishing agent cylinders under high pressure
WARNING Risk of death due to pressure in extinguishing agent cylinders.
If pressurized extinguishing agent cylinders are damaged and extinguishing agent
escapes uncontrollably, there is a risk of severe injuries.
• Do not transport or store extinguishing agent cylinders unless they are sealed with a protec-
• Ensure that the extinguishing agent cylinders are attached correctly.
• Replace damaged extinguishing agent cylinders immediately.
2.5.2 Dangers when the system is activated
Cold extinguishing agent
WARNING Risk of injury from cold extinguishing agent.
The extinguishing agent exiting at the discharge nozzles is very cold. Direct contact
may result in injury.
• Leave the extinguishing zone without delay and within the pre-discharge timer when an
• Stay out of the direct flow area of a discharge nozzle.
14
alert.
clear.
tive valve cap and a lock nut.
alarm is given.