Operation
FIGURE 6-4: Container valve
The quick release valve is installed on an extinguishing agent container and can be opened pneu-
matically, electrically or manually. When the valve is open, the extinguishing agent flows through
the pipelines to the extinguishing nozzles.
The valve works according to the differential pressure system. By activating a release device, the
pilot valve integrated in the valve is opened and the upper pressure chamber is vented abruptly.
This drop in pressure causes the extinguishing agent container pressure to press the closing pis-
ton in the opened position, thereby opening the valve.