The pneumatic control device is used to activate:
Extinguishing agent container batteries
Selector valves
Pneumatic control and alarm components
An 80 l pilot cylinder is used.
The pneumatic control device can additionally be connected to a reserve pilot cylinder via a shut-
tle non-return valve.
Pilot cylinder with wall support
FIGURE 4-20: Pilot cylinder with unistrut racking
1. Protective cap
2. Locking nut
3. Pilot cylinder
4. Unistrut racking
Nitrogen (N
The pilot cylinders are designed, manufactured, and labeled in accordance with American guide-
lines (DOT) or in accordance with the country-specific pressure equipment guidelines.
A type plate is attached to each pilot cylinder. For safety reasons, all pilot cylinders must be
mounted using a wall support set on stable building elements (e.g. a wall).
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en
) is stored as control gas in pilot cylinders with a volume of 80 l (21.13 gal).
2
Design and Function
49