Viking Oxeo PR LCP Operator's Manual page 50

Inert gas extinguishing system
Table of Contents

Advertisement

Design and Function
Pneumatic control device
FIGURE 4-19: Pneumatic control device
1. Steel cylinder (pilot cylinder) UL/FM QRV-TD 80 l N
Contact pressure gauge UL Oxeo 2901 psi (200 bar), NO under pressure (part no. 927612)
Contact pressure gauge UL Oxeo 2901 psi (200 bar), NC under pressure (part no. 927615)
2. Release device, electrical, QRV (part no. 914027D)
3. Pneumatic pilot line (precision steel pipe)
4. Monitoring of electric release device QRV
The pneumatic control device is installed standing on the floor and fastened to a wall using a
wall bracket set. The pneumatic control device is activated by an electrical release device.
When activated, a release pin is activated in the electric release device. The release pin opens
the pilot cylinder valve. The control gas then flows through the pressure reducer into the con-
nected pneumatic pilot line to the pneumatic system parts of the fire extinguishing system.
48
200 (part no. 4003404)
2
Operator's Manual | Oxeo PR LCP | F_101821 Rev 02 | 08-2022 | en

Advertisement

Table of Contents
loading

Related Products for Viking Oxeo PR LCP

Table of Contents