Clp Slot - Siemens SIMATIC CloudConnect CC7 Series Operating Instructions Manual

Industrial ethernet
Table of Contents

Advertisement

Pressing the button
Duration of pressing
Function and operation
the button (seonds)
≥ 5 s
Resetting to factory settings
1. Turn off the power supply.
2. Switch the power supply on again while pressing the button.
3. Release the button when the LED stops flashing.
Once reset is complete, the gateway performs a restart and can be reached using the default IP
address set at the factory.
2.4

CLP Slot

The slot for an optional CLP is located on the back of the module.
For information on inserting and removing the CLP, see section Using a CLP (Page 44).
Figure 2-2
SIMATIC CC7
Operating Instructions, 10/2019, C79000-G8976-C503-02
Hold down the button for at least 5 seconds during startup.
Reset is prepared while the "Diagnosis" LED flashes.
While the LED lights up with a green steady light, the gateway performs the reset.
Slot for optional CLP on the back of the device
LEDs, Connectors, Buttons, CLP
2.4 CLP Slot
29