Configuration
4.10 Data points
When using other data types in the device and in downstream applications, you must map
and interpret the data read from the station in a user-specific manner.
Restrictions for MindConnect IoT Extension
The following data is not supported:
● Time stamp
● With S7-LINT / S7-ULINT:
Integers from 2
The following data types are only supported when they are transferred as event:
● Bool
● String
4.10.3

Import tags

In addition to manual data point configuration, you can import the tag information using a file
exported from STEP 7 for S7 stations.
Note that all data points manually configured beforehand are deleted during import of tag
information from STEP 7 files.
After importing tags from STEP 7 files, you can manually configure more data points.
Observe the following limits for the import:
● Maximum number of tags per file: 5000
● Maximum number of tags per station: 5000
The value also applies to the import of multiple files.
● Maximum number of elements per S7 array: 500
Requirement: Creating CPU tags in STEP 7
As a prerequisite for using the function, you need to have created tags or symbols in the
respective CPU in your STEP 7 project.
● STEP 7 Professional (TIA Portal)
– DB tags
– PLC tags
● STEP 7 V5.6
– DB tags
– Symbols
108
to 2
63
64
The "Optimized block access" option must be disabled in DBs.
Operating Instructions, 10/2019, C79000-G8976-C503-02