2.2 Parameter description
2.2.3

Interference frequency suppression

The frequency of your AC power system can interfere with the measured value especially
when measuring in low voltage ranges and using thermocouple elements. Here, enter the
mains frequency in your system (50 Hz or 60 Hz).
The interference frequency suppression parameter applies to all analog electronic modules.
With this parameter, you also specify the integration and conversion time of the various
modules. See the technical data for the analog electronic modules.
2.2.4

Reference junction slot

This parameter allows you to assign a slot (none or 2 to 12) with a channel for measuring the
reference temperature (calculation of the compensation value).
Reference
For information on connecting thermocouples, refer to the
modules
2.2.5

Reference junction input

This parameter can be used to set the channel (0/1) for measuring the reference
temperature (calculation of the compensation value) for the assigned slot.
Reference
For information on connecting thermocouples, refer to the
modules
12
.
.
manuals
for the
manuals
for the
IM151-1 BASIC interface module (6ES7151-1CA00-0AB0)
Manual, 07/2008, A5E01075925-02
analog electronic
analog electronic