Dimension Drawing - ABB ACH580-31 Hardware Manual

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC
PTC terminal current
Short-circuit detec-
tion
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and wiring
are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-
02 PTC terminal.
Relay output (62...63)
Maximum wire size
Maximum contact
rating
Maximum breaking
capacity
External power supply (40...41)
Maximum wire size
Input voltage
Maximum power con-
sumption
Isolation areas
1

Dimension drawing

The dimensions are in millimeters and [inches].
< 1 mA
< 50 ohm ±10%
1.5 mm 2
250 V AC / 30 V DC / 5 A
1000 VA
1.5 mm 2
24 V AC / V DC ±10% (GND, user potential)
25 W, 1.04 A at 24 V DC
24 V
in
Plugged to drive SLOT2
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
CMOD-02
1
interface) 281
RO PTC
PTC
in