ABB ACH580-31 Hardware Manual page 183

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

ACH580-
Input current
31-...
A
156A-4
134
180A-4
163
3-phase U n = 480 V
09A5-4
7.0
12A7-4
9.0
018A-4
12.0
026A-4
17.0
033A-4
24
039A-4
29
046A-4
34
062A-4
44
073A-4
54
088A-4
66
106A-4
82
145A-4
111
169A-4
134
206A-4
163
1.
Fuses are required as part of the installation, are not included in the base drive
configuration and must be provided by others.
2. Fuses with a higher current rating than specified must not be used.
3. The UL listed fuses recommended by ABB are the required branch circuit
protection per NEC. Circuit breakers listed in section Circuit breakers (UL) are
also acceptable as branch circuit protection.
4. The recommended size or smaller UL listed 248 fast acting, time delay, or high
speed fuses must be used to maintain the UL listing of the drive. Additional
protection can be used. Refer to local codes and regulations.
5. A fuse of a different class can be used at the high fault rating where the I
2
and I
t of the new fuse is not greater than that of the specified fuse.
6. UL listed 248 fast acting, time delay, or high speed fuses from other
manufacturers can be used if they meet the same class and rating requirements
specified in the rules above.
7. When installing a drive, always follow ABB installation instructions, NEC
requirements and local codes.
8. Alternative fuses can be used if they meet certain characteristics. For
acceptable fuses, see the manual supplement (3AXD50000645015).
UL (one fuse per phase)
Nominal cur-
Voltage rating
rent
A
225
300
15
20
25
35
40
50
60
80
90
110
150
200
225
300
Bussmann
type
V
600
JJS-225
600
JJS-300
600
JJS-15
600
JJS-20
600
JJS-25
600
JJS-35
600
JJS-40
600
JJS-50
600
JJS-60
600
JJS-80
600
JJS-90
600
JJS-110
600
JJS-150
600
JJS-200
600
JJS-225
600
JJS-300
Technical data 183
UL class
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
peak