ABB ACH580-31 Hardware Manual page 138

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

138 Control unit
Connection
X4 Safe Torque Off
4)
4)
X10 24 V AC/DC
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Digital inputs DI1...DI5 also support 10...24 V AC.
Terminal sizes (all terminals): 0.14 ... 2.5 mm 2 (26...14 AWG)
Tightening torques: 0.5 ... 0.6 N·m (4.4 ... 5.3 lbf·in)
Wire strip length 7...8 mm (0.3 in)
Notes:
1)
Current [0(4)...20 mA, R in = 100 ohm] or voltage [0(2)...10 V, R in >200 kohm]. Change
of setting requires changing the corresponding parameter.
2)
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on the board.
3)
In scalar control: See Menu > Primary settings > Start, stop, reference > Constant
speeds / constant frequencies or parameter group 28 Frequency reference chain.
In vector control: See Menu > Primary settings > Start, stop, reference > Constant
speeds / constant frequencies or parameter group 22 Speed reference selection.
DI3
Scalar control (default)
0
Set frequency through AI1
1
28.26 Constant frequency 1
Term
29
B+
29
30
A-
30
31
31
DGND
S4
S4
TERM
S5
S5
BIAS
34
OUT1
34
35
OUT2
35
36
36
SGND
37
37
IN1
38
38
IN2
40
24 V
40
AC/DC+
41
in
41
24 V
AC/DC- in
Operation/Parameter
Description
Embedded fieldbus, EFB (EIA-485)
Termination switch
Bias resistors switch
Safe torque off. Factory connection.
Both circuits must be closed for the
drive to start.Refer to
off function (page
External 24 V AC/DC input to power
up the control unit when the main
supply is disconnected. 7)
Vector control
Set frequency through AI1
22.26 Constant speed 1
The Safe torque
221).