ABB ACH580-31 Hardware Manual page 106

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

106 Electrical installation – IEC
10. Connect the cables:
Ground the shield 360° by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable.
Connect the twisted shield of the cable to the grounding terminal.
Connect the additional PE conductors (if any).
For frame R8: Install the common mode filter. For instructions, see
mode filter kit for ACS880-01 frame R7, and for ACS880-11, ACS880-31,
ACH580-31 and ACQ580-31 frame R8 installation instructions
(3AXD50000015179
Connect the phase conductors of the motor cable to the T1/U, T2/V and
T3/W terminals and the phase conductors of the input cable to the L1, L2
and L3 terminals.
If the DC cables are present, cut off one phase conductor and isolate the
end.
Connect the remaining conductors to the UDC+ and UDC- terminals.
Tighten the screws to the torque given in the installation drawing below.
[English]).
PE
Common

Advertisement

Table of Contents
loading

Table of Contents