106 Electrical installation – IEC
10. Connect the cables:
•
Ground the shield 360° by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable.
•
Connect the twisted shield of the cable to the grounding terminal.
•
Connect the additional PE conductors (if any).
•
For frame R8: Install the common mode filter. For instructions, see
mode filter kit for ACS880-01 frame R7, and for ACS880-11, ACS880-31,
ACH580-31 and ACQ580-31 frame R8 installation instructions
(3AXD50000015179
•
Connect the phase conductors of the motor cable to the T1/U, T2/V and
T3/W terminals and the phase conductors of the input cable to the L1, L2
and L3 terminals.
•
If the DC cables are present, cut off one phase conductor and isolate the
end.
Connect the remaining conductors to the UDC+ and UDC- terminals.
•
Tighten the screws to the torque given in the installation drawing below.
[English]).
PE
Common