CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 273
Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module
indicate the motor speed 0...1500 rpm with a frequency range of 0...10000 Hz.
Parameter
15.22 DO1 configuration
15.33 Freq out 1 source
15.34 Freq out 1 src min
15.35 Freq out 1 src max
15.36 Freq out 1 at src min
15.37 Freq out 1 at src max
■
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
Color
Green
Technical data
Installation
Degree of protection
Ambient conditions
Package
Reley outputs (50...52, 53...55)
Maximum wire size
Minimum contact rat-
ing
Maximum contact
rating
Maximum breaking
capacity
Transistor output (42...44)
Maximum wire size
Type
Description
The extension module is powered up.
Into an option slot on the drive control unit
IP20 / UL Type 1
See the drive technical data.
Cardboard
1.5 mm 2
12 V / 10 mA
250 V AC / 30 V DC / 2 A
1500 VA
1.5 mm 2
Transistor output PNP
Setting
Frequency output
01.01 Motor speed used
0
1500.00
1000 Hz
10000 Hz