Layout And Example Connections - ABB ACH580-31 Hardware Manual

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

278 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated
PTC interface)
There is reinforced insulation between the motor thermistor connection, the relay
output and the drive control unit interface. Thus, you can connect a motor
thermistor to the drive through the extension module.
With CCU-24 control unit, a CMOD-02 module is not necessary for external
24 V AC/DC supply connection. The external supply is connected directly to
terminals 40 and 41 on the control unit.

Layout and example connections

3
3
2-pin terminal block for external power
supply
24 V AC/DC
40
24 V AC/DC
External 24 V (AC/DC) in-
+ in
put
41
24 V AC/DC
External 24 V (AC/DC) in-
- in
put
1
+
40
24V AC/DC + in
-
24V AC/DC - in
41
6
4
2-pin terminal block for relay output
RO PTC C
62
63
RO
PTC B
X4
OUT1
34
OUT2
35
SGND
36
IN1
37
IN2
38
62
RO PTC C
Common, C
63
RO PTC B
Normally open, NO
4
5
2
CMOD-02
CCU