Start-Up; Setting The Parameters - ABB ACH580-31 Hardware Manual

Industrial drives
Hide thumbs Also See for ACH580-31:
Table of Contents

Advertisement

272 CMOD-01 multifunction extension module (external 24 V AC/DC and digital
I/O)
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered using an external 24 V AC supply.

Start-up

Setting the parameters

1.
Power up the drive.
2. If no warning is shown,
make sure that the value of both parameters 15.01 Extension module type
and 15.02 Detected extension module is CMOD-01.
If the warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 is CMOD-01.
set the parameter 15.01 value to CMOD-01.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
3. Set the parameters of the extension module to applicable values.
Examples are given below.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate
the reverse direction of rotation of the motor with a one-second delay.
Parameter
15.07 RO4 source
15.08 RO4 ON delay
15.09 RO4 OFF delay
Parameter setting example for digital output
This example shows how to make digital output DO1 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
Parameter
15.22 DO1 configuration
15.23 DO1 source
15.24 DO1 ON delay
15.25 DO1 OFF delay
Setting
Reverse
1 s
1 s
Setting
Digital output
Reverse
1 s
1 s

Advertisement

Table of Contents
loading

Table of Contents