Harmony Series H2 Mortise Lock
*IMPORTANT: Pin 7 must be tied to earth ground in the access control panel.
Failure to follow proper ESD safe grounding procedures could lead to equipment failure.
Typical Harmony Mortise Lock Application Diagram (12/24VDC System)
Standard Application Shown - For Alternative Applications Contact 1-800-810-WIRE (9473)
Reader Electronics Require 12 or 24VDC UL294 Listed, Power Limited Power Supply (or UL603)
12/24VDC System
Reader Draw = 150mA @12 or 24VDC
Actuator Draw = 15mA continuous
Total system Draw = 550mA @12/24VDC
12 Conductor
ElectroLynx Harness
From McKinney
Harmony Series H2
NOTE:
If your lock is configured with End of Line Resistors,
reference instruction sheet A8191 for the wiring of
RX & DPS outputs.
A8027G • 800-810-WIRE (9473) • www.sargentlock.com
This product is polarity sensitive; if the lock
does not operate, check the polarity of the
input and reverse if necessary.
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
QC12 Electric
DATA 0 - Green, 4
Hinge From
McKinney
RX (NO/NC) - Orange, 5
RX (COM) - Blue, 6
*EGND- Brown, 7
LED - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
H
N
120 VAC
12/24VDC
Input
-
+
Lock body
ULC-S319 compliance:
EAC power supply utilizing battery backup
Power Supply
(30 minutes operation) is required.
(By Others)
Not Used
5
Reader Electronics
G
Require 12 or 24VDC UL294 Listed,
Power Limited Power Supply (or UL603)
UL294 Listed
EAC Panel
Electronic
(-)
Access
12/24VDC
(+)
Control
DATA 1
Panel
DATA 0
(By Others)
RX
Use (NC) for
RX
Fail Safe
Operation
Lock Relay
DPS
DPS
(NO) Fail
Secure
Operation