5.12 Installation and fixing material without additional earthquake stabilization
Before installing the individual components, the installation and fixing material required has to be prepared.
Floor fixing versions:
Version with bolted floor fixing
Fig. 7: Bolted floor fixing
(1)
Upper edge of finished floor
Floor fixing plate (holder for profiles at a
distance ≥ 1200 mm), Fig. 10 "Side view of the fixing
(2)
plate"
(3)
C-profile CB 50 x 30 x 3, EN 10025, S235JR
Hook-head bolt M16x35-4.6-galvanized
(4)
Washer ISO 7094 - 16 - 100 HV
Hexagon nut ISO 4032 – M16 – 8
(5)
Base frame of panel
(6)
Min. 50 mm
110-0084.9 / 15
NOTICE
Damages due to corrosion
Welded seams are susceptible to corrosion.
After welding, protect the welded seams professionally against corrosion.
Foundation
Double floor
NXAIR /
Bolted
floor fixing
possible
possible
(7)
Min. 90 mm
(8)
80 mm
(9)
Raw floor
Expansion dowel with hexagon
(10)
head bolt and washer: FAN 12/10
(11)
Floor finish
──
──
≤
40 kA
Preparing installation
Welded
floor fixing
possible
not possible
19