Switchgear With Absorber - Siemens NXAIR Installation Instructions Manual

Medium-voltage switchgear
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

To install the switchgear, the switchgear room must have certain minimum dimensions.
Depending on the room height, the pressure relief system of the switchgear must be designed with evacuation
ducts leading out of the switchgear building:
Switchgear with
evacuation ducts
Switchgear with
evacuation ducts
or absorber
5.5

Switchgear with absorber

Fig. 5: Dimensions of the switchgear room, absorber
For panel replacement: Control aisle ≥ 1250 mm
1)
For connection from the rear: ≥ 500 mm; also valid with rear connection duct
2)
For contactor panel with panel width 435 mm: ≥ 100 mm
For a panel depth of 1540 mm: ≥ 110 mm
For further information, see information drawings NXAIR, order number 110-2300.9.
110-0084.9 / 15
Height of switchgear
Rated voltage
room [mm]
≥ 2500
≥ 2800
≥ 3000
≥ 3500
≥ 3500
NXAIR /
40 kA
Preparing installation
Rated short-time
withstand current
U
[kV]
r
I
[kA]
k
≤ 17.5
≤ 40
≤ 12
≤ 25
≤ 12
31.5
≤ 31.5
17.5
≤ 17.5
40
B = panel width / T = panel depth
complete
13