Electrical connections

10.7 Dimensions of three-core cables

The most important dimensions of indoor sealing ends for three-core cables are the permissible length and
diameter of the sealing ends, as well as the length of the cable lug up to and including the heat-shrinkable
splitting cap.
The bolts for the cable sealing ends are already pre-assembled at the cable connection and must not be
changed.
Diameter of
cable sealing end
Length from cable lug
up to and including
heat-shrinkable
splitting cap
Length of cable sealing
end, incl. cable lug
Cable cross-section
1
2
Fig. 224: Dimensions of three-core cables
(except for contactor panel with panel
width 435 mm)
156
(except for contactor panel with panel
width 435 mm)
≤ 12 kV
U
r
max. 60 mm
max. 500 mm
max. 300 mm
max. 240 mm ²
(1)
Length of cable sealing end, incl. cable lug
Length from cable lug up to and including heat-
(2)
shrinkable splitting cap
(3)
Diameter of cable sealing end
NXAIR /
All versions
U
= 17.5 kV
r
max. 60 mm
max. 500 mm
max. 300 mm
max. 240 mm ²
3
Fig. 225: Dimensions of three-core cables in contactor
panel with panel width 435 mm (side view)
40 kA
Contactor panel with
panel width 435 mm
≤ 12 kV
U
r
max. 60 mm
max. 500 mm
max. 300 mm
max. 240 mm ²
110-0084.9 / 15