Siemens NXAIR Installation Instructions Manual page 144

Medium-voltage switchgear
Hide thumbs Also See for NXAIR:
Table of Contents

Advertisement

Accessing the connection compartment through the rear
Fig. 211: All panel versions except for contactor panels with panel width 435 mm
Access to the connection compartment through the rear side of the panel is given.
Contactor panels with panel width 435 mm only:
Remove the connecting elements from one of the vertical ledges (1):
Remove the vertical ledge, and store it together with the associated connecting elements.
Proceed in the same way with the other vertical ledge.
Fig. 212: Contactor panels with panel width 435 mm only:
144
and switch-disconnector panel: Removing the rear wall
15 bolts M8x20 with contact washers
30 bolts in the ledges
NXAIR /
(4) Rear wall with handle
4
(5) Bolts to loosen
5
1
(1) Vertical ledges
40 kA
110-0084.9 / 15