Closing the connection compartment / connection duct
Procedure
Installation of the rear wall is described hereafter by the example of a 3-panel arrangement.
Fig. 287: All panel versions except for contactor
All panel versions except for contactor panels with panel width 435 mm and switch-
disconnector panel:
At the rear side of the panel, insert the rear wall (1) by the handle, and push it down.
Fix the rear wall by screwing the bolts at the bottom hand-tight:
Tighten the bolts with a tightening torque of 25 Nm.
Fig. 289: All panel versions except for contactor panels with panel width 435 mm and switch-
194
panels with panel width 435 mm:
Rear wall, 3-panel arrangement
4 bolts M8x20 with contact washers (2)
disconnector panel: Installing and fixing the rear wall
NXAIR /
Fig. 288: Contactor panels with panel width
435 mm only:
Rear wall,
3-panel arrangement
1
(1) Rear wall with handle
(2) Bolts to screw
2
40 kA
110-0084.9 / 15